Description
Description
Standards
-
ProductNF C33-209
Application
NF C 33-209 service bundled conductors are used for tributary networks of power buildings and their internal networks.
Characteristics
The bundled conductor cables have aluminum (or copper ) conductors, insulated with XLPE, they have good durability and thermal resistance.
Some other important cable characteristics are :
- Ultraviolet radiation resistance,
- Ozone resistance,
- High dielectric strength,
- Light and easy to handle.
Installation
The NF C 11-201 standard´s procedures determine the installation procedures for low voltage overhead lines.
These cables are NOT ALLOWED to be buried, even in conduits.
Electrical characteristics
- Rated voltage : 0.6/1 kV
- Test voltage : 4 kV AC
- Resistance to voltage surges : 1.2/50µs with a positive or negative polarity and a peak value of 20 kV.
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Solid
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE (chemical)
Outer sheath
PE
Dimensional characteristics
Dimensional characteristics
Conductor cross-section
16 mm²
Number of cores
4
Approximate diameter of the bunched cable
18.8 mm
Approximate weight
274 kg/km
Maximum outer diameter
18.8 mm
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
1.91 Ohm/km
Permissible current rating in open air
- A
Rated Voltage Uo/U (Um)
0,6/1 kV
Voltage drop, 3 conductors
3.44 V/A.km
Usage characteristics
Usage characteristics
Length
1000 m
Packaging
-
Flame retardant
No
Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania